APPLICATION
Connection between optical distribution panels and equipment
FEATURES
100% pre-terminated and tested in factory to ensure transfer performance
Reduction of installation time
Fire retardant in conformity with IEC 60332-3C standard
No corrosive gas emissions IEC 60754-2 standard
Low smoke zero halogen emissions with IEC 61034-2 standard
Using standard LC, SC, ST, FC connectors, supporting simplex or duplex
Customized products available
PRODUCT PHOTOS
PRODUCT PARAMETERS
Performance Level | Standard | Elite |
Connector | Mode | Endface | IL(max) (dB) | RL(min) (dB) | IL(max) (dB) | RL(min) (dB) |
MPO/MTP | SM | 12F/APC | ≤0.70 | ≥60 | ≤0.35 | ≥60 |
24F/APC | ≤0.75 | ≥60 | ≤0.35 | ≥60 |
MM | 12F/PC | ≤0.50 | ≥20 | ≤0.35 | ≥20 |
24F/PC | ≤0.50 | ≥20 | ≤0.35 | ≥20 |
LC/SC/FC/ST | SM | APC | ≤0.30 | ≥60 | ≤0.10 | ≥60 |
UPC | ≤0.20 | ≥50 | ≤0.10 | ≥50 |
MM | PC | ≤0.20 | ≥30 | ≤0.10 | ≥30 |
Note:
1.Test wavelength:SM@1310/1550nm,MM@850/1300nm;
2.Standard conformance: GR-326,GR-1435.
Mechanical Properties |
Item | Criteria | Conformance |
△IL After 50 Matings | MPO/MTP | ≤0.3dB | GR-1435 |
△IL After 500 Matings | LC/SC/FC/ST | ≤0.2dB | IEC 61300-2-2 |
Min Bend Radius (Dynamic) | 20*OD (Cable Diameter) |
Min Bend Radius (Static ) | 15*OD (Cable Diameter) |
Environment Conditions |
Item | Criteria | Conformance |
Operation Temperature | -40~60°C | IEC 61753-1 |
Storage Temperature | -45~85°C |